Field Paint System for structural, utility, piping, Equipment, Hydrocarbon Pumps, Hydrocarbon lines (For Temperature less than 90° C) (Un-insulated CS Lines):
Surface Preparation : SA-2 1/2
Primer Coat : Inorganic Zinc Silicate Coating : DFT : 70 microns
Intermediate Coat : Polyamide Cured High Build Epoxy Micaceous Iron Oxide Coat : DFT : 100 microns
Final Coat : Acrylic Polyurethane Finish Paint : Two Coats : DFT 60 microns each.
Total DFT : 230 Microns.
Painting System for Galvanised Pipe and Galvanised Surfaces.
Surface Preparation : ST.2
Primer Coat : Etch Primer : DFT : 8 microns
Intermediate Coat : Zinc Phosphate Epoxy Primer : DFT : 50 microns.
Final Coat : Acrylic Polyurethane Finish Paint : Two Coats : DFT 40 microns each.
Total DFT : 138 microns.